Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

187

Appendix

E

Configuration Parameters

This appendix lists parameters that can be configured via the Logix Designer
application.

Topic

Page

Table 17 Safety Digital Input Parameters

187

Table 18 Test Output Parameters

188

Table 19 Safety Digital Output Parameters

188

Table 20 Safety Analog Input Parameters

188

Table 17 - Safety Digital Input Parameters

Parameter Name

(1)

Value

Description

Default

x

Input Delay Time
Off -> On

0…126 ms (in increments of
6 ms)

Filter time for OFF to ON transition.

x

Input Delay Time
On -> Off

0…126 ms (in increments of
6 ms)

Filter time for ON to OFF transition.

x

Input Point Mode

Not Used

External input device is not connected.

Safety Pulse Test

Use with a contact output device and in combination with a test output. Using this setting, short-
circuits between input signal lines and the power supply (positive side) and short-circuits between
input signal lines can be detected.

Safety

A solid-state output safety sensor is connected.

Standard

A standard device, such as a reset switch, is connected.

x

Safety Input Test Source

Not Used

The test output that is used with the input.

Test Output 0

Test Output 1

Test Output 2

Test Output 3

x

Input Point Operation Type

Single Channel

Use as single channel.

Dual-channel Equivalent

Use as dual-channel. Normal when both channels are ON or OFF.

Dual-channel Complementary

Use as dual-channel. Normal when one channel is ON and the other channel is OFF.

x

Safety Input Error Latch Time

0…65,530 ms
(in increments of 10 ms)

Safety input or test output errors are latched for this time.

1000 ms