Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

111

Configure the Module for a SmartGuard Controller

Chapter 6

2. Click the Safety Configuration tab.

3. Double-click each set of input points to edit their configuration.

Parameter Name

Value

Description

Default

Input Point Operation Type

Single Channel

Use as single channel.

Single

Dual-channel Equivalent

Use as dual-channel. Normal when both channels are ON or OFF.

Dual-channel Complementary

Use as dual-channel. Normal when one channel is ON and the other channel is
OFF.

Input Point Mode

Not Used

External input device is not connected.

Not Used

Safety Pulse Test

Use with a contact output device and in combination with a test output. Using
this setting, short-circuits between input signal lines and the power supply
(positive side) and short-circuits between input signal lines can be detected.

Safety

A solid-state output safety sensor is connected.

Standard

A standard device, such as a reset switch, is connected.