Chapter 2

Safety Inputs, Safety Outputs, and Safety Data

POINT Guard I/O Analog Input Module

These are the safe states of the POINT Guard I/O analog input module:

Safety input data to network in single-channel configuration: 0 (OFF)
Safety input data to network in dual-channel equivalent configuration:

If a diagnostic fault occurs, the signal for the faulted channel is set to 0

(OFF).

If a dual-channel discrepancy fault occurs, the dual-channel inputs

continue to report actual input signals.

Safety Inputs (1734-IB8S)

Safety inputs are used to monitor safety input devices.

Using a Test Output with a Safety Input

A test output can be used in combination with a safety input for short circuit,
cross-channel, and open-circuit fault detection. Configure the test output as a
pulse test source and associate it to a specific safety input.

Figure 4 - Example Use of a POINT Guard I/O Input Module

TIP

The test output can also be configured as a power supply to source 24V DC
to an external device, for example, a light curtain.

I0

I1

I4

I5

I2

I3

I6

I7

COM

COM

COM

COM

TO

T1M

T2

T3M

0

2

4

6

1

3

5

7

0

2

4

6

1

3

5

7

Where:
T0 = Test Output 0

T1M = Test Output 1 with Muting

T2 = Test Output 2

T3M = Test Output 3 with Muting

I0…I7 = Safety Inputs

Safety Input
Terminal

External
Contact