Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 189

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

189

Configuration Parameters

Appendix E

x

Input Point Operation Type

Single channel

Use as single channel.

Single

Dual channel

Use as a dual channel equivalent. This setting should be used only with
SmartGuard controllers.

Filter

1 Hz

Input filter

1 Hz

5 Hz

10 Hz

50 Hz

x

Safety Input Error Latch Time

0…65,530 ms
(in 10 ms increments)

Safety input errors are latched for this time so that they can be read by the
controller and are not missed if they clear themselves too quickly. One value for all
channels.

1000

Low Engineering

-30000…30000

Scaling value for inputs

0

High Engineering

-30000…30000

Scaling value for inputs

10,000

(2)

x

Tachometer Dual Low
Diagnostic

ON/OFF

Diagnostic that indicates if both channels are low.
Channels 0 and 1 share the same value and channels 2 and 3 share the same value.

Off

Tachometer Trigger

Falling edge (NPN)

Non-inverted input signal.

Falling edge

Rising edge (PNP)

Inverted input signal.

Tachometer Off Level

0…23V
(in 1 V increments)

Off-level for the Tachometer mode input signal.

5V

Tachometer On Level

1…24V
(in 1 V increments)

On-level for the Tachometer mode input signal.

11V

Sensor Power Mode

External

Sensors are getting their power from a separate power supply.

Module

x

Module

Sensors are getting their power from the module (recommended).

Alarm Enable

Disable

Enable or disable alarms.
We recommend disabling this feature when using the module in a GuardLogix
system (evaluate alarms using the application program). Enable this feature when
using the module in a SmartGuard system.

Disable

Enable

High High Alarm Level

-32768…32767

High High alarm trip point.

32767

Low Low Alarm Level

-32768…32767

Low Low alarm trip point.

-32767

High High - Low Low
Deadband

0…32767

Deadband on the High High and Low Low alarms.

0

High Alarm

-32768…32767

High alarm trip point.

332767

Low Alarm

-32768…32767

Low alarm trip point.

0

High - Low Deadband

0…32767

Deadband on the High and Low alarms.

0

x

Discrepancy Time

0…65,530
(in 10 ms increments)

Time period during which the channel values may be discrepant before an error is
reported.

100 ms

x

Discrepancy Deadband

0…32767

Tolerance range between channels in dual-channel mode (in engineering units)

0

x

Channel Offset

-32768…32767

Offset value for dual channel mode only (in engineering units).

0

(1) Parameters directly related to safety are marked with an x in the left column.
(2) 1000 for Tachometer mode.

Table 20 - Safety Analog Input Parameters (continued)

Parameter Name

(1)

Value

Description

Default

Advertising