Install the Module

Chapter 4

Figure 37 - 3-wire Voltage or Tachometer Sensor (SIL 3)

Figure 38 - 3-wire Current Sensor (SIL 3)

Follow the

Guidelines for Wiring Safety Analog Inputs on page 65

.

V0

V1

V2

V3

I0

I1

I2

I3

COM

COM

COM

COM

S0

FE

S1

S2

S3

FE

This wiring configuration may also be used for SIL 2 redundant Tachometer mode.
For analog voltage-output sensors, the signal levels for operation for the application must be outside the signal level when the signal is not
present, for example, when the wire is broken.
Field sensors are monitoring the same signal in a redundant configuration.

You must configure a safety discrepancy deadband between the two signals to achieve SIL 3.

SIL 2

3-wire
Sensor

1734-TB Terminal Bases

Signal (V)

+24V

Cable Shield

Cable Shield

+24V

SIL 2

3-wire
Sensor

Signal (V)

Signal Return

Signal Return

See

Figure 43

and

Figure 44 on page 72

for tachometer wiring detail.

V0

V1

V2

V3

I0

I1

I2

I3

COM

COM

COM

COM

S0

FE

S1

S2

S3

FE

For 0…20 mA analog current-output sensors, the signal levels for operation for the application must be outside the signal level when the signal
is not present, for example, when the wire is broken.
Field sensors are monitoring the same signal in a redundant configuration.

You must configure a safety discrepancy deadband between the two signals to achieve SIL 3.

SIL 2

3-wire
Sensor

1734-TB Terminal Bases

Signal (I)

+24V

Cable Shield

Cable Shield

+24V

SIL 2

3-wire
Sensor

Signal (I)

Signal Return

Signal Return