Distributed I/O communication for safety I/O data is performed through safety
connections supporting CIP Safety over an EtherNet/IP or DeviceNet network.
Data processing is performed in the safety controller. The status and fault
diagnostics of POINT Guard I/O modules are monitored by a controller.

In addition to I/O state data, the modules include status data for monitoring I/O
faults within each circuit.

The configuration information of the modules can be protected by a password.

1734-IB8S Digital Input Module Features

Safety digital inputs

Safety devices, such as emergency stop push buttons, gate switches, and

safety light curtains, can be connected.

Dual-channel mode evaluates consistency between two input signals

(channels), which allows use of the module for safety Category 3 and 4
and in applications rated up to and including Performance Level e/
SIL CL3.

Single-channel mode evaluates one input signal (channel), which allows

use of the module for safety Category 2 and in applications rated up to
and including Performance Level d/SIL CL 2.

You can configure a discrepancy time to control how long two channels

are allowed to be discrepant before a fault is declared.

An external wiring short-circuit check is possible when inputs are wired

in combination with test outputs. The module must be wired in
combination with test outputs when this function is used.

Independently adjustable on and off delays are available per channel.

Test outputs (digital input modules only)

Separate test outputs are provided for short-circuit detection of a safety

input (or inputs).

Power (24V) can be supplied to devices, such as safety sensors.
Test outputs can be configured as standard outputs.
Specific test outputs can be used for broken-wire detection of a muting

lamp.

1734-OB8S Safety Digital Output Module Features

Solid-state outputs
Dual-channel mode provides redundant control by using two output

signals (channels), which allows use of the module for safety Category 3
and 4, and applications rated up to and including Performance Level e/
SIL CL3.

Safety outputs can be pulse-tested to detect field wiring short circuits to

24V DC.