Appendix B

Get I/O Diagnostic Status from Modules in Logix Systems

This sample ladder logic is monitoring the status of output point 3. This ladder
logic rung examines the Output Point Status and, when a fault is detected
(0 = error), the message instruction is executed.

Configure the
Message Instruction

Follow this procedure to edit the Message Configuration dialog box.

1. In the Message Instruction in the ladder logic, click the

icon.

2. On the Configuration tab, enter the appropriate data for what you want to

monitor.
a. From the Service Type pull-down menu, choose Get Attribute Single.
b. Enter the Class, Instance, and Attribute data, referring to the

appropriate tables on pages

157

158

.

3. On the Communication tab, specify the path for the message.

This example illustrates values you enter to determine the reason for the fault on
Output 3.

Figure 48 - Message Instruction Configuration Example

TIP

When entering the Instance value, enter the input/output point plus 1
In this example, Output Point 3 is Instance 4.