Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

175

Specifications

Appendix C

Input filter time, OFF to ON

(3)

0…126 ms (in 6 ms increments)

Input filter time, ON to OFF

(2)

Terminal base screw torque

See terminal base specifications

Indicators

1 yellow lock status indicator
1 green/yellow power status indicator
8 I/O channel status indicators

Keyswitch positions (left and right)

Key 1 = 8 (left); Key 2 = 1 (right)

North America temp code

T4

IEC temp code

T4

Enclosure type rating

None (open-style)

Wiring category

(4)

2 - on signal ports

Wire size

Determined by installed terminal block

Weight, approx.

62.4 g (2.2 oz)

Dimensions (HxWxD), approx. (without terminal block)

77 x 25 x 55 mm (3.03 x 0.98 x 2.17 in.)

(1) Maximum power dissipation applies when using 28.8V DC module supply, 30V DC on all inputs and maximum power dissipated

with all four test outputs in the ON state.

(2) Typical power dissipation applies when using 24V DC module supply, 24V DC on all inputs and nominal power dissipated with all

four test outputs in the ON state.

(3) Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off time is the time from a

valid input signal to recognition by the module.

(4) Use this conductor category information for planning conductor routing. Refer to the Industrial Automation Wiring and Grounding

Guidelines, publication

1770-4.1

.

Attribute

1734-IB8S Series B