Chapter 5

Configure the Module in a GuardLogix Controller System

4. Specify the general properties of the Ethernet adapter.

a. In the Name field of the New Module dialog box, type the name of the

1734 Ethernet adapter.

b. In the Description field, type a description, if desired.
c. In the IP Address field, type the IP address.

5. Click Change to edit the Ethernet Adapter’s Module Definition.

.

a. In the Revision fields, choose the major and minor revisions.

b. From the Electronic Keying pull-down menu, choose the appropriate

keying method.

IMPORTANT

1734-AENT adapter firmware must be major revision 3 or later to
support POINT Guard I/O modules.

Choose

Description

Exact Match

Module and type series must exactly match or the module will be rejected by the
controller.

Compatible Module

Controller will check module type and revision for compatibility. Compatible
modules that match or are newer will be accepted.

Disable Keying

Controller will check module type, but will accept any version. Do not choose
Disable Keying.