Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

25

Safety Inputs, Safety Outputs, and Safety Data

Chapter 2

Figure 5 - Test Pulse in a Cycle

For the 1734-IB8S module, the pulse width (X) is typically 525 μs; the pulse
period (Y) is typically 144 ms.

When the external input contact is closed, a test pulse is output from the test
output terminal to diagnose the field wiring and input circuitry. By using this
function, short-circuits between inputs and 24V power, and between input signal
lines and open circuits can be detected.

Figure 6 - Short-circuit between Input Signal Lines

X

OUT

Y

On

Off

IN+

24V

24V

0V

COM

T0

T1

IN0

IN1

External Contact

Short-circuit between Input Signal Lines and Power
Supply (positive side)

External Contact

Short-circuit between Input Signal Lines

44079