Safety Data

Appendix D

Figure 62 - PFD vs. Proof Test Interval 1734-OB8S Series A

Mission Time for all modules is 20 years.

PFD

Proof Test Interval [years]

Cat. No.

Proof Test Interval

(Mission Time)

PFD

PFH

(1/hour)

Spurious Trip Rate (STR)

(2)

(2) Calculated based on ISA TR-84 method.

MTTF

spurious

(3)

(years)

(3) Mean Time to Failure (Spurious).

Year

Hour

1734-IB8S
Series A

1

8760

2.11E-06

5.10E-10

2.666E-06

42.78

2

17520

4.23E-06

5

43800

1.06E-05

10

87600

2.11E-05

20

175200

4.23E-05

1734-OB8S
Series A

1

8760

2.13E-06

5.14E-10

3.229E-06

35.33

2

17520

4.27E-06

5

43800

1.07E-05

10

87600

2.13E-05

20

175200

4.27E-05

1734-IE4S
Series A

1

8760

1.6E-07

3.7E-11

9.402E-07

121.42

2

17520

3.2E-07

5

43800

8.1E-07

10

87600

1.6E-06

3.8E-11

10

(1)

(1) This data is for dual channel mode of operation.

87600

2.4E-06

5.5E-11

20

175200

3.3E-06

3.9E-11