Resetting a module to out-of-box condition, By using the logix designer application – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 139

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

139

Replacing POINT Guard I/O Modules

Chapter 8

Figure 45 - Setting the SNN with a GuardLogix Controller

Figure 46 - Setting the SNN with a SmartGuard Controller

Resetting a Module to
Out-of-box Condition

If a POINT Guard I/O module was used previously, clear the existing
configuration before installing it on a safety network.

By Using the Logix Designer Application

When the Logix Designer application is online, the Safety tab of the Module
Properties dialog box displays the current configuration ownership. When the
opened project owns the configuration, Local is displayed. When a second device
owns the configuration, Remote is displayed, along with the safety network
number (SNN), and node address or slot number of the configuration owner.
Communication error is displayed if the module read fails.

When using POINT Guard I/O with a

See

GuardLogix controller on an EtherNet/IP network

By Using the Logix Designer Application on page 139

GuardLogix controller with 1734-PDN module on a
DeviceNet network

By Using RSNetWorx for DeviceNet Software on page 140

SmartGuard controller on a DeviceNet network