Chapter 8

Replacing POINT Guard I/O Modules

1. Remove the old I/O module and install the new module.

2. Right-click your POINT Guard I/O module and choose Properties.

3. Click the Safety tab.

4. Click Reset Ownership.

5. Click OK.

6. Follow your company-prescribed procedures to functionally test the

replaced I/O module and system and to authorize the system for use.

If

then

the module is in out-of-box condition

go to step

6

.

No action is needed for the GuardLogix controller to take
ownership of the module.

an SNN mismatch error occurs

go to the next step to reset the module to out-of-box condition.