Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 1

POINT Guard I/O Overview

Verify that the POINT Guard I/O firmware revision is correct prior to
commissioning the safety system. Firmware information for safety I/O modules
is available at

http://www.rockwellautomation.com/products/certification/safety

.

Verify that a safety administrator conducts a risk assessment on the machine and
determines module suitability before installation.

TIP

Field power must be applied to the 1734-IE4S module when updating
firmware.

ATTENTION: Personnel responsible for the application of safety-related
programmable electronic systems (PES) shall be aware of the safety
requirements in the application of the system and shall be trained in using the
system.

ATTENTION: Use only appropriate components or devices complying with
relevant safety standards corresponding to the required safety category and
safety integrity level.

Conformity to requirements of the safety category and safety integrity level

must be determined for the entire system.

We recommend you consult a certification body regarding assessment of

conformity to the required safety integrity level or safety category.

You are responsible for confirming compliance with the applicable standards for
the entire system.

Table 1 - Requirements for Controlling Devices

Device

Requirement

Allen-Bradley Bulletin Safety Components

Emergency stop switches

Use approved devices with direct opening mechanisms complying with IEC/EN 60947-
5-1.

Bulletin 800F, 800T

Door interlocking switches,
limit switches

Use approved devices with direct opening mechanisms complying with IEC/EN 60947-
5-1 and capable of switching microloads of
24V DC, 3 mA.

Bulletin 440K, 440G, 440H for interlock switch
Bulletin 440P, 802T for limit switch

Safety sensors

Use approved devices complying with the relevant product standards, regulations, and
rules in the country where used.

Any Guardmaster product

Relays with forcibly- guided
contacts, contactors

Use approved devices with forcibly-guided contacts complying with EN 50205. For
feedback purposes, use devices with contacts capable of switching micro loads of
24V DC, 3 mA.

Bulletin 700S, 100S

Other devices

Evaluate whether devices used are appropriate to satisfy the requirements of safety
category levels.

-