Table 18 test output parameters, Table 19 safety digital output parameters, Table 20 safety analog input parameters – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 188

Advertising
background image

188

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Appendix E

Configuration Parameters

Table 18 - Test Output Parameters

Parameter Name

(1)

Value

Description

Default

x

Test Output Mode

Not Used

An external device is not connected.

Not Used

Standard

The output is connected to a standard device.

Pulse Test

A contact output device is connected. Use in combination with a safety
input.

Power Supply

The power supply of a Safety Sensor is connected. The voltage supplied to I/
O power (V, G) is output from the test output terminal.

Muting Lamp Output (Terminal T1
or T3 only)

An indicator is connected and turned ON to detect broken lines in an
external indicator.

Test Output Fault Action

Clear OFF

Action to perform when a communication error is detected.

Clear OFF

Hold Last Data

(1) Parameters directly related to safety are marked with an x in the left column.

Table 19 - Safety Digital Output Parameters

Parameter Name

(1)

Value

Description

Default

x

Output Point Mode

Not Used

An external output devices is not connected.

Not Used

Safety

When the output is ON, the test pulse is not output (remains ON).

Safety Pulse Test

Using this function, short-circuits between output signal lines and the power
supply (positive side) and short-circuits between output signal lines can be
detected.

x

Output Point Operation Type

Single Channel

Use as single channel.

Dual-channel

Dual-channel

Use as dual-channel. When both channels are normal, outputs can be turned ON.

x

Safety Output Error Latch
Time

0…65,530 ms
(in increments of 10 ms)

Safety output errors are latched for this time.

1000 ms

(1) Parameters directly related to safety are marked with an x in the left column.

Parameter Name

Value

Description

Default

Test Output Idle State

(1)

Clear OFF or Keep Output Data

Definition of output data is in idle state.

Clear OFF

(1) Set only through explicit messaging. Refer to for

Appendix B

more information.

Table 20 - Safety Analog Input Parameters

Parameter Name

(1)

Value

Description

Default

x

Input Point Mode

Not Used

External input device is not connected.

Not Used

Safety

A solid-state safety sensor is connected.

Standard

A device that is not used in the safety loop is connected.

Range

±10V

Input voltage range.

4…20 mA

0…5V

0…10V

±5V

4…20 mA

Input current range.

0…20 mA

Tachometer

Tachometer mode.