152

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Appendix A

Indicators

Module

Network Status

Configuration Lock

Indicator

Description

Recommended Action

MS

Off

No power is applied to the module.

Apply power to this connector.

Solid green

The module is operating normally.

None.

Solid red

The module detected an unrecoverable fault.

Cycle power to the module. If problem persists, replace the module.

Flashing green

Device is in the Idle or Standby state.

Configure the module and establish connection.

Flashing red

The module has detected a recoverable fault.

Cycle power to the module or reset the module.

User-initiated firmware update is in progress.

Wait for firmware update to complete.

Flashing red and
green

Module is not configured.

Reconfigure the module. For additional information, inspect Network
Status indicator.

The module is performing its power-cycle diagnostic tests.

Wait for the module to complete its power-cycle diagnostics.

Indicator

Description

Recommended Action

NS

Off

The module is not online with the network or there is no power.

Verify your network is working properly.

Flashing green

Module online with no connections in established state.

Verify your network and module configuration.

The module identified the communication rate of the network but no
connections are established.

Solid green

Module online with connections in established state. The module is
operating normally.

None.

Flashing red

One or more I/O connections is in timed-out state.

Verify your network and module configuration.

A user-initiated firmware update is in progress.

Wait for firmware update to complete.

Solid red

Critical link failure. The module detected an error that prevents it
from communicating on the network, such as a duplicate node
address.

Cycle power to the module. Check node addressing.

Indicator

Description

Recommended Action

LK

(1)

Off

No configuration or configured by a GuardLogix originator.

Validate configuration by a network configuration tool, such as
RSNetWorx software.

Invalid configuration data.

Solid yellow

Locked.

None.

Valid configuration, locked by a network configuration tool, such as
RSNetWorx software.

Flashing yellow

Not locked.

None.

Valid configuration by a network configuration tool, such as
RSNetWorx software.

(1) Not applicable when used with GuardLogix controllers.