Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 197

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

197

I/O Assemblies

Appendix F

864 (360h)

32

Input Type (Dual Channel Mode)

4B

2

1

Safety Input 1 Configuration Data

33

Input Range

49

2

3

34

Input Channel Mode

49

2

4

35

Filter Setting

49

2

36

Input Error Latch Time (Low Byte)

49

2

8

37

Input Error Latch Time (High Byte)

49

2

8

38

Low Engineering (Low Byte)

49

2

14

39

Low Engineering (High Byte)

49

2

14

40

High Engineering (Low Byte)

49

2

15

41

High Engineering (High Byte)

49

2

15

42

Tach Dual Low Check

49

2

104

43

Tach Trigger

49

2

105

44

Tach OFF Level

49

2

106

45

Tach ON Level

49

2

107

46

Sensor Power Mode

49

2

103

47

High High/Low Low Alarm Enable

49

2

17

48

High High/Low Low Alarm Trip High (Low Byte)

49

2

18

49

High High/Low Low Alarm Trip High (High Byte)

49

2

18

50

High High/Low Low Alarm Trip Low Low(Low Byte)

49

2

19

51

High High/Low Low Alarm Trip Low Low(High Byte) 49

2

19

52

High High/Low Low Alarm Deadband (Low Byte)

49

2

20

53

High High/Low Low Deadband (High Byte)

49

2

20

54

Pad Byte (Reserved)

49

55

High/Low Alarm Enable

49

2

22

56

High/Low Alarm Trip High (Low Byte)

49

2

23

57

High/Low Alarm Trip High (High Byte)

49

2

23

58

High/Low Alarm Trip Low (Low Byte)

49

2

24

59

High/Low Alarm Trip Low (High Byte)

49

2

24

60

High/Low Alarm Deadband (Low Byte)

49

2

25

61

High/Low Alarm Deadband High Byte)

49

2

25

62

Pad Byte 1

63

Pad Byte 2

Table 27 - Configuration Assemblies for 1734-IE4S Input Modules (continued)

Instance Decimal
(hex)

Byte

Field

Class
(hex)

Instance
(decimal)

Attribute
(decimal)

Description