Mission time for all modules is 20 years – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 185

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

185

Safety Data

Appendix D

Figure 64 - PFD vs Proof Test Interval 1734-OB8S Series B

Mission Time for all modules is 20 years.

Catalog
Number

Year

Hour

PFD (1/hour)

PFH (1/hour)

Spurious Trip
Rate (STR)

(2)

(2) Calculated based on ISA TR-84 method.

MTTFspur
(years)

(3)

(3) Mean Time to Failure (Spurious).

1734-IB8S
Series B

(1)

(1) Data for this module is for both single channel and dual channel modes of operation.

1

8760

2.18E-06

5.27E-10

2.709E-06

42.14

2

17520

4.36E-06

5

43800

1.09E-05

10

87600

2.18E-05

20

175200

4.36E-05

1734-OB8S
Series B

1

8760

2.16E-06

5.20E-10

3.243E-06

35.20

2

17520

4.32E-06

5

43800

1.08E-05

10

87600

2.16E-05

20

175200

4.32E-05