Add and configure the 1734 ethernet adapter – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 75

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

75

Configure the Module in a GuardLogix Controller System

Chapter 5

5. Click Change to edit the Module Definition.

a. In the Revision fields, choose the major and minor revisions.
b. From the Electronic Keying pull-down menu, choose the appropriate

keying method.

6. Click OK.

The I/O Configuration tree displays the Ethernet connection.

Add and Configure the 1734
Ethernet Adapter

1. Right-click the Ethernet connection and choose New Module.

2. On the Select Module dialog box, check Communication and

Allen-Bradley.

3. Choose an Ethernet adapter from the list and click Create.

Choose

Description

Compatible Module

Allows a module to determine whether it can emulate the module
defined in the configuration sent from the controller.

Disable Keying

None of the parameters in the physical module and module
configured in the software must match.
Do not choose Disable Keying.

Exact Match

All of the parameters must match or the inserted module rejects a
connection to the controller.