Dual-channel mode and discrepancy time – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 27

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

27

Safety Inputs, Safety Outputs, and Safety Data

Chapter 2

Dual-channel Mode and Discrepancy Time

To support dual-channel safety devices, the consistency between signals on two
channels can be evaluated. Either equivalent or complementary can be selected.

If the length of a discrepancy between the channels exceeds the configured
discrepancy time (0…65,530 ms in increments of 10 ms), the safety input data
and the individual-safety input status turn off for both channels. In Dual-channel
Complimentary mode, the safety input data goes to off/on for input channels
n/n+1 respectively as described in

Table 3

.

This table shows the relation between input terminal states and controller input
data and status.

IMPORTANT

The dual-channel function is used with two consecutive inputs that are paired
together, starting at an even input number, such as inputs 0 and 1, 2 and 3,
and so on.

IMPORTANT

If you are using the safety application instructions with a GuardLogix
controller, set the module’s inputs to Single (default). Do not use the modules’
dual-channel mode as this functionality is provided by the safety application
instructions.

Table 3 - Terminal Input Status and Controller I/O Data

Dual-channel Mode

Input Terminal

Controller Input Data and Status

Dual-channel
Resultant
Data

Dual-channel
Resultant

IN0

IN1

Safety
Input 0 Data

Safety
Input 1 Data

Safety
Input 0 Status

Safety
Input 1 Status

Dual-channels, Equivalent

OFF

OFF

OFF

OFF

ON

ON

OFF

Normal

OFF

ON

OFF

OFF

OFF

OFF

OFF

Fault

ON

OFF

OFF

OFF

OFF

OFF

OFF

Fault

ON

ON

ON

ON

ON

ON

ON

Normal

Dual-channels, Complementary OFF

OFF

OFF

ON

OFF

OFF

OFF

Fault

OFF

ON

OFF

ON

ON

ON

OFF Normal

ON

OFF

ON

OFF

ON

ON

ON Normal

ON

ON

OFF

ON

OFF

OFF

OFF

Fault

Advertising