Appendix F

I/O Assemblies

Using Data from Modules
Configured via the Generic
Profile

To use I/O assembly data from a 1734-IE4S module configured via the Generic
Profile in your application program, you must first combine the input data from
two SINTs into a single INT. The following example shows one method for
converting the data by using a Move instruction and a Bit Field Distribute
instruction.

EXAMPLE

This example uses Input Assembly Instance 802, which is described on
page

193

.

POINTGuardAnalogMod.I.Data[0] = Channel 0 Low Byte (SINT)
POINTGuardAnalogMod.I.Data[1] = Channel 0 High Byte (SINT)
CH0_Data = Combined Channel 0 data (INT) that can be used in an

application program