Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 97

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

97

Configure the Module in a GuardLogix Controller System

Chapter 5

Follow these steps to configure alarms for each of the safety analog input
channels.

1. From the Module Properties dialog box, click the Alarm tab.

2. To configure each channel, click 0, 1, 2, or 3, as appropriate.

3. To enable the alarm, check the boxes:

Enable High High - Low Low Alarms
Enable High - Low Alarms

4. Type the alarm values from -32768…32767 in the appropriate fields,

following these guidelines:
The High High alarm value must be greater than or equal to the High

alarm value.

The High alarm value must be greater that the Low alarm value.
The Low Low alarm value must be less than or equal to the Low alarm

value.

These values are based on the Engineering units configured on

page 96

.

5. Configure a deadband value for the High High - Low Low alarms and

High - Low alarms, if desired.

The valid range is 0…32767. The deadband lets the alarm status bit remain
set, despite the alarm condition disappearing, as long as the input data
remains within the deadband of the alarm. These values are based on the
Engineering units configured on

page 96

.

For more information on this feature, see

Process Alarms on page 33