Safety outputs (1734-ob8s), Safety output with test pulse, Dual-channel mode – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 39: Safety output with test pulse dual-channel mode

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

39

Safety Inputs, Safety Outputs, and Safety Data

Chapter 2

Safety Outputs (1734-OB8S)

Read this section for information about safety outputs.

Safety Output with Test Pulse

When the safety output is on, the safety output can be configured to pulse test
the safety output channel. By using this function, you can continuously test the
safety output’s ability to remove power from the module’s output terminals. If an
error is detected, the safety output data and individual safety output status turn
off.

Figure 18 - Test Pulse in a Cycle

For the 1734-OB8S module, the pulse width (X) is typically 475 μs; the pulse
period (Y) is typically 575 ms.

Dual-channel Mode

When the data of both channels is in the on state, and neither channel has a fault,
the outputs are turned on. The status is normal. If a fault is detected on one
channel, the safety output data and individual safety output status turn off for
both channels.

Figure 19 - Dual-channel Setting (not to scale)

IMPORTANT

To prevent the test pulse from causing the connected device to malfunction,
pay careful attention to the input response time of the output device.

44096

X

Y

OUT

On

Off

ON

OFF

OUT0

Safety Output
0, 1
Status

OUT0

OUT1

OUT1

Safety Output
0, 1
Status

Fault Detection

Error
Detected

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Normal Operation

Safety
I/O
Network
Data Sent
to the
Controller

Safety
I/O
Network
Data Sent
to the
Controller

Advertising