Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 174

Advertising
background image

174

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Appendix C

Specifications

1734‐IB8S Series B temperature versus aggregate current
per module ‐ derating for both horizontal and vertical
installations

Pulse width

525

μs

Pulse period

144 ms

Maximum field capacitance limit permitted per test
output

100 nF

Current, max (when used to control muting lamp)

25 mA (to avoid fault when used as a muted lamp output)

Current, min (when used to control muting lamp)

5 mA (at which fault indication is generated when used as
a muted lamp output)

Residual voltage, max

0.3 V

Output leakage current, max

0.1 mA

Short circuit protection

Yes

POINTBus

POINTBus current, max

110 mA

Power dissipation, max

(1)

3.0 W

Thermal dissipation, max

10.25 BTU/hr

Power dissipation, typical

(2)

2.25 W

Isolation Voltage

50 V (continuous), Basic Insulation Type between field
side and system.
No isolation between individual channels.
Type tested at 500V AC for 60 s.

Power bus, operating supply voltage

24V DC nom, Class 2

Power bus, operating voltage range

19.2…28.8V DC, Class 2

Power bus current (no load), max

25 mA

Attribute

1734-IB8S Series B

2.8 A

-20 °C
(-4 °F)

40 °C
(104 °F)

55 °C
(131 °F)

0.55 A