Table 27 - Configuration Assemblies for 1734-IE4S Input Modules

Instance Decimal
(hex)

Byte

Field

Class
(hex)

Instance
(decimal)

Attribute
(decimal)

Description

864 (360h)

0

Input Type (Dual Channel Mode)

4B

1

1

Safety Input 0 Configuration Data

1

Input Range

49

1

3

2

Input Channel Mode

49

1

4

3

Filter Setting

49

1

4

Input Error Latch Time (Low Byte)

49

1

8

5

Input Error Latch Time (High Byte)

49

1

8

6

Low Engineering (Low Byte)

49

1

14

7

Low Engineering (High Byte)

49

1

14

8

High Engineering (Low Byte)

49

1

15

9

High Engineering (High Byte)

49

1

15

10

Tach Dual Low Check

49

1

104

11

Tach Trigger

49

1

105

12

Tach OFF Level

49

1

106

13

Tach ON Level

49

1

107

14

Sensor Power Mode

49

1

103

15

High High/Low Low Alarm Enable

49

1

17

16

High High/Low Low Alarm Trip High (Low Byte)

49

1

18

17

High High/Low Low Alarm Trip High (High Byte)

49

1

18

18

High High/Low Low Alarm Trip Low Low(Low Byte)

49

1

19

19

High High/Low Low Alarm Trip Low Low(High Byte) 49

1

19

20

High High/Low Low Alarm Deadband (Low Byte)

49

1

20

21

High High/Low Low Deadband (High Byte)

49

1

20

22

Pad Byte (Reserved)

49

23

High/Low Alarm Enable

49

1

22

24

High/Low Alarm Trip High (Low Byte)

49

1

23

25

High/Low Alarm Trip High (High Byte)

49

1

23

26

High/Low Alarm Trip Low (Low Byte)

49

1

24

27

High/Low Alarm Trip Low (High Byte)

49

1

24

28

High/Low Alarm Deadband (Low Byte)

49

1

25

29

High/Low Alarm Deadband High Byte)

49

1

25

30

Pad Byte 1

31

Pad Byte 2