Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 2

Safety Inputs, Safety Outputs, and Safety Data

Overfrequency Bit Operation

When the frequency exceeds 1 kHz, the module reports a data value of 1 kHz,
sets the Overfrequency status bit to 0, and latches it. While the Overfrequency
bit is set to 0, you must use an alternate method to monitor the frequency of the
system because the value reported by the module is latched at 1 kHz. Once you
have verified that the frequency is lower than 1 kHz, you may reset the
Overfrequency condition by setting the Reset Tach bit, which lets the module
begin measuring the frequency of field pulses again.

If you set the Reset Tach bit while the frequency is still above 1 kHz, the
Tachometer Overfrequency bit transitions to 1 (within range) momentarily.
However, as soon as the module begins measuring pulses, it will detect another
overfrequency condition and immediately set the Tachometer Overfrequency bit
to 0 again. The Reset Tach bit is edge-sensitive.

See

Output Assemblies on page 192

for more information on resetting the

Overfrequency bit.

Figure 17 - Overfrequency Operation

In

Figure 17

, the module reports a frequency of 0 Hz until the frequency of the

system reaches 1 Hz at A, when the module begins reporting the actual value. At
B, the frequency exceeds 1 kHz, the Overfrequency bit is set to 0, and the module
continues to report a data value of 1 kHz. Between B and C, you must monitor
the frequency by an alternate method because the value reported by the module
may not be accurate. After C, the Overfrequency condition can be cleared,
provided you have used an alternate method to verify that the actual frequency is
below 1 kHz.

ATTENTION: Before resetting the Overfrequency condition, you must use
another method to verify that the actual frequency is lower than 1 kHz.

A

B

C

1 kHz

1 Hz

Frequency = 0

Actual values are

reported.

Monitor frequency via an

alternate method.

Overfrequency

condition can be

cleared.

Frequency = 1 Hz

Overfrequency bit is set to 0.
Frequency = 1000 Hz