Configure digital safety outputs – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 113

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

113

Configure the Module for a SmartGuard Controller

Chapter 6

6. Double-click Test Output Points to edit their configuration.

7. Click Apply and OK.

Configure Digital Safety Outputs

1. Double-click each group of Outputs Points to display the parameters for

editing.

2. Double-click Output Error Latch Time to change from the default value

(1000ms), if desired.

Parameter Name

Value

Description

Default

Test Output Mode

Not Used

An external device is not connected.

Not Used

Standard

The output is connected to a standard device.

Pulse Test

A contact output device is connected. Use in combination with a safety input.

Power Supply

The power supply of a Safety Sensor is connected. The voltage supplied to I/O power (V, G) is
output from the test output terminal.

Muting Lamp Output
(Terminal T1 or T3 only)

An indicator is connected and turned ON to detect broken lines in an external indicator.

Parameter Name

Value

Description

Default

Output Point Mode

Not Used

An external output devices is not connected.

Not Used

Safety

When the output is ON, the test pulse is not output (remains ON).

Safety Pulse Test

Using this function, short-circuits between output signal lines and the power supply (positive side)
and short-circuits between output signal lines can be detected.

Output Point Operation
Type

Single Channel

Use as single channel.

Dual-channel

Dual-channel

Use as dual-channel. When both channels are normal, outputs can be turned ON.

Safety Output Error Latch
Time

0…65,530 ms
(in 10 ms increments)

Safety output errors are latched for this time.

1000 ms