Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 4

Install the Module

Figure 39 - 4-wire Voltage or Tachometer Sensor (SIL 3)

Figure 40 - 4-wire Current Sensor (SIL 3)

Follow the

Guidelines for Wiring Safety Analog Inputs on page 65

.

FE

FE

V0

V1

V2

V3

I0

I1

I2

I3

COM

COM

COM

COM

COM

COM

COM

COM

S0

S1

S2

S3

S0

S1

S2

S3

This wiring configuration may also be used for SIL 2 redundant Tachometer mode.
Signal Return and Common are at the same potential.
Field sensors are monitoring the same signal in a redundant configuration.

You must configure a safety discrepancy deadband between the two signals to achieve SIL 3.

SIL 2

4-wire
Sensor

1734-TOP3 Terminal Bases

Signal (V)

+24V

Cable Shield

Signal Return

Common

SIL 2

4-wire
Sensor

Signal (V)

+24V

Signal Return

Common

Cable Shield

See

Figure 43

and

Figure 44 on page 72

for tachometer wiring detail.

FE

FE

V0

V1

V2

V3

I0

I1

I2

I3

COM

COM

COM

COM

COM

COM

COM

COM

S0

S1

S2

S3

S0

S1

S2

S3

Signal Return and Common are at the same potential.
Field sensors are monitoring the same signal in a redundant configuration.
You must configure a safety discrepancy deadband between the two signals to achieve SIL 3.

SIL 2

4-wire
Sensor

1734-TOP3 Terminal Bases

Signal (I)

+24V

Cable Shield

Signal Return

Common

SIL 2

4-wire
Sensor

Signal (I)

+24V

Signal Return

Common

Cable Shield