Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 112

Advertising
background image

112

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 6

Configure the Module for a SmartGuard Controller

4. If you are pulse-testing the module, edit the parameters so that the

channels are pulse tested by Test sources 0 and 1, respectively.

5. Double-click General to edit the Input Error Latch Time, if desired.

The default value is 1000 ms.

Safety Input Test Source

None

The test output that is used with the input.

None

Test Output 0

Test Output 1

Test Output 2

Test Output 3

Input Delay Time Off -> On

0…126 ms (in 6 ms increments)

Filter time for OFF to ON transition.

0 ms

Input Delay Time On -> Off

0…126 ms (in 6 ms increments)

Filter time for ON to OFF transition.

0 ms

Parameter Name

Value

Description

Default

Advertising