124

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 6

Configure the Module for a SmartGuard Controller

Save and Download Module
Configuration

We recommend that after a module is configured you save your work

If the MS and NS status indicators on the POINT Guard I/O module are not
both solid green after download, ownership may have been lost. The ownership is
based on the following:

POINT Guard I/O module number
POINT Guard I/O safety network number
SmartGuard slot number
SmartGuard safety network number
Path from SmartGuard controller to POINT Guard I/O module
Configuration signature

If any of these change, the connection between the SmartGuard controller and
the POINT Guard I/O module is lost, and a yellow yield icon appears in the
RSNetWorx for DeviceNet tree. For more information, see

Chapter 8

.

IMPORTANT

If you have not followed the configuration guidelines in the parameter tables
found in

Configure Safety Analog Inputs on page 114

, the error message

“Invalid Configuration Parameter? occurred while attempting to configure the
safety device” appears in the Error Log during download.