Figure 4-27. Programmable Functions Settings

A

Auto Transfer Switch Input: Select Input (None, 1-16) and Contact Recognition (Always or While

Engine Running Only).

B

Grounded Delta Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine

Running Only).

C

Battle Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine Running

Only).

D

Low Line Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine

Running Only).

E

Single Phase Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine

Running Only).

F

Single Phase AC Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine

Running Only).

G

Battery Charger Fail: Select Input (None, 1-16), Alarm Configuration (None, Alarm, Pre-Alarm),

Activation Delay (s) (0 to 300 in increments of 1), and Contact Recognition (Always or While Engine
Running Only).

H

Low Coolant Level: Select Input (None, 1-16), Alarm Configuration (None, Alarm, Pre-Alarm),

Activation Delay (s) (0 to 300 in increments of 1), and Contact Recognition (Always or While Engine
Running Only).

I

Fuel Leak Detect: Select Input (None, 1-16), Alarm Configuration (None, Alarm, Pre-Alarm), Activation

Delay (s) (0 to 300 in increments of 1), and Contact Recognition (Always or While Engine Running Only).

Remote LSM Inputs
An optional LSM-2020 (Load Share Module) provides one configurable

A

contact input that can be used as

a setpoint source for Var, PF, or kW control. Settings are provided for min and max input voltage

B

, and

min and max input current

C

. Refer to Bias Control Settings in this section for information selecting the

LSM-2020 input as a setpoint source.
BESTCOMSPlus settings for the remote LSM input (DGC-2020, Programmable Inputs, Remote LSM
Inputs) are illustrated in Figure 4-29.