NOTES

1.) If the CEM-2020 is providing one end of the J1939 bus, a 120

 terminating

resistor should be installed across terminals P1- LO (CANL) and P1- HI
(CANH).

2.) If the CEM-2020 is not part of the J1939 bus, the stub connecting the CEM-

2020 to the bus should not exceed 914 mm (3 ft) in length.

3.) The maximum bus length, not including stubs, is 40 m (131 ft).

4.) The J1939 drain (shield) should be grounded at one point only. If grounded

elsewhere, do not connect the drain to the CEM-2020.

AEM-2020

(Optional)

CEM-2020

Other

Devices

P0053-60

Engine

120 ohm

Termination

CAN-H

CAN-L

LSM-2020

(Optional)

DGC-2020

120 ohm

Termination

Bus

Stub

Figure 9-3. CANbus Interface with CEM-2020 providing One End of the Bus

AEM-2020

(Optional)

DGC-2020

Other

Devices

P0053-61

Engine

120 ohm

Termination

CAN-H

CAN-L

LSM-2020

(Optional)

CEM-2020

120 ohm

Termination

Bus

Stub

Figure 9-4. CANbus Interface with DGC-2020 providing One End of the Bus

MAINTENANCE

Preventive maintenance consists of periodically checking that the connections between the CEM-2020
and the system are clean and tight. Contact Expansion Modules are manufactured using state-of-the-art
surface-mount technology. As such, Basler Electric recommends that no repair procedures be attempted
by anyone other than Basler Electric personnel.

9-6

DGC-2020 CEM-2020 (Contact Expansion Module)

9400200990 Rev K