Functional description, Analog inputs, Rtd inputs – Winco DGC-2020 User Manual

Page 247: Thermocouple inputs, Analog outputs, Communications, Canbus, Bestcomsplus software, Installation, Product registration

Advertising
background image

9400200990 Rev K

DGC-2020 AEM-2020 (Analog Expansion Module)

10-3

FUNCTIONAL DESCRIPTION

A functional description of the AEM-2020’s inputs and outputs is provided below.

Analog Inputs

The AEM-2020 provides eight analog inputs that are user-selectable for 4 to 20 mA or 0 to 10 Vdc. Each
analog input has under/over thresholds that can be configured as status only, alarm, or pre-alarm. When
enabled, an out of range alarm alerts the user of an open or damaged analog input wire. The label text of
each analog input is customizable.

RTD Inputs

The AEM-2020 provides eight user-configurable RTD inputs for monitoring genset temperature. Each
RTD input can be configured as status only, alarm, or pre-alarm to protect against high or low
temperature conditions. When enabled, an out of range alarm alerts the user of an open or damaged
RTD input wire. The label text of each RTD input is customizable.

Thermocouple Inputs

The AEM-2020 provides two thermocouple inputs for monitoring genset temperature. Each thermocouple
input can be configured as status only, alarm, or pre-alarm to protect against high or low temperature
conditions. When enabled, an out of range alarm alerts the user of an open or damaged thermocouple
input wire. The label text of each thermocouple input is customizable.

Analog Outputs

The AEM-2020 provides four analog outputs that are user-selectable for 4 to 20 mA or 0 to 10 Vdc. A
wide selection of parameters including oil pressure, fuel level, generator voltage, and bus voltage can be
configured as analog outputs. Refer to Section 4, BESTCOMSPlus Software, for a full list of parameter
selections.

Communications

CANbus

A Control Area Network (CAN) is a standard interface that enables communication between the AEM-
2020 and the DGC-2020.

BESTCOMSPlus SOFTWARE

BESTCOMSPlus provides the user with a point-and-click means to set and monitor the Analog Expansion
Module. Installation and operation of BESTCOMSPlus is described in Section 4, BESTCOMSPlus
Software.

INSTALLATION

Analog Expansion Modules are delivered in sturdy cartons to prevent shipping damage. Upon receipt of a
module, check the part number against the requisition and packing list for agreement. Inspect for
damage, and if there is evidence of such, immediately file a claim with the carrier and notify the Basler
Electric regional sales office, your sales representative, or a sales representative at Basler Electric,
Highland, Illinois USA.

If the device is not installed immediately, store it in the original shipping package in a moisture- and dust-
free environment.

Product Registration

Registering with Basler Electric enables you to receive important information updates on your product
plus new product announcements. Register your product by directing your web browser to

www.basler.com

.