Bestlogic+ composition, Bestlogic+ composition -2, I/o -2 – Winco DGC-2020 User Manual

Page 164: Table 5-1. i/o group, names and descriptions -2

Advertising
background image

BESTlogic+ Composition

There are three main groups of objects used for programming BESTlogic+. These groups are I/O,
Components,
and Elements. For details on how these objects are used to program BESTlogic+, see the
paragraphs on Programming BESTlogic+.

I/O

This group contains Input Objects, Output Objects, Alarms, Pre-Alarms, and Senders. Table 5-1 lists the
names and descriptions of the objects in the I/O group.

Table 5-1. I/O Group, Names and Descriptions

Name Description

Symbol

Input Objects

Logic 0

Always FALSE (Low).

Logic 1

Always TRUE (High).

Physical Inputs

IN1 - IN16

TRUE when Physical Input x is active.

Remote Inputs

IN17 - IN26

True when Remote Input x is active.
(Available when an optional CEM-2020 is
connected.)

Virtual Inputs

VIN1 - VIN4

TRUE when Virtual Input x is active.

Status Input

Analog Expansion
Module

Analog Expansion Module Connected. TRUE when
an optional AEM-2020 is connected to the DGC-
2020.

Analog Expansion
Module

Remote Analog
Inputs 1-8

TRUE when Over 1, Over 2, Under 1, Under 2, or
Out of Range is configured as Status Only and the
threshold has been exceeded. (Over 1 shown.)

Analog Expansion
Module

Remote Analog
Outputs 1-4

TRUE when the analog output connection is open
and the Out of Range Alarm Configuration is set to
Status Only.

Analog Expansion
Module

Remote RTD Inputs
1-8

TRUE when Over 1, Over 2, Under 1, Under 2, or
Out of Range is configured as Status Only and the
threshold has been exceeded. (Over 1 shown.)

Analog Expansion
Module

Remote
Thermocouple
Inputs 1-2

TRUE when Over 1, Over 2, Under 1, Under 2, or
Out of Range is configured as Status Only and the
threshold has been exceeded. (Over 1 shown.)

Status Input

ATS Input

TRUE when the ATS (Auto Transfer Switch) input is
TRUE.

Status Input

Audible Horn

TRUE when the Audible Horn is active.

Status Input

Auto Mode

TRUE when the DGC-2020 is in Auto Mode.

5-2

DGC-2020 BESTlogic+ Programmable Logic

9400200990 Rev K