GENERAL SETTINGS

General DGC-2020 settings consist of settings controlling the HMI display and indicators. Additional
general settings include style number configuration, DGC-2020 identification, DGC-2020 version
information, and device security setup.

Front Panel HMI
The contrast

A

of the front panel LCD (liquid crystal display) can be adjusted to suit the viewing angle used

or compensate for environmental conditions.
A power saving feature, referred to as Sleep mode

B

, will turn the front panel LCD backlight and LCD

heater off when the DGC-2020 is in Off mode or Auto mode (not in Run mode) and a key is not pressed
for more than 15 minutes. Normal display operation is resumed when any front panel button is pressed or
the genset is started remotely via the ATS. Sleep mode is enabled and disabled in BESTCOMSPlus.
Specific language modules can be uploaded into the DGC-2020. When the language module upload is
complete, use the Language

C

selector to select the correct language.

When Scrolling Screen is enabled

D

, the front panel summary screen will scroll through the list of Scrolling

Screen Items

E

. The Scrolling Screen Delay

F

determines the scrolling speed. When this feature is disabled

only VOLT, AMP, PH, Hz, OIL, FUEL, TEMP, and BATT are shown on the front panel summary screen.
The phase values are toggled at a rate defined by the Phase Toggle Delay

G

setting. When the phase

toggle delay is set to zero, information for each phase is obtained by pressing the Up or Down arrow keys
on the front panel HMI.
Two custom initializing messages

HI

are displayed on the initial boot screen of the DGC-2020.

BESTCOMSPlus front panel HMI settings are illustrated in Figure 4-11.

Figure 4-11. Front Panel HMI Settings

A

LCD Contrast Value: Adjustable from 0 to 100 (maximum contrast) in increments of 1.

B

Front Panel Sleep Mode: Enable or Disable.

C

Language: English, Chinese, or Spanish.

D

Scrolling Screen Enable: Enable or Disable.

E

Configurable HMI Summary Settings: Select Scrolling Screen Item 1 through 20.

F

Scrolling Screen Delay: Adjustable from 1 to 120 s in 1 s increments.

G

Phase Toggle Delay: Adjustable from 0 to 20 s in 1 s increments.

H

Initializing Message 1: Accepts an alphanumeric string of up to 16 characters. Displayed on the second

line of the initial boot screen.

I

Initializing Message 2: Accepts an alphanumeric string of up to 16 characters. Displayed on the third

line of the initial boot screen.