Alarms, High coolant temperature, Low oil pressure – Winco DGC-2020 User Manual

Page 112: Overspeed, Low fuel level, Low coolant level, Alarms -42

Advertising
background image

4-42

DGC-2020 BESTCOMSPlus Software

9400200990 Rev K

F

Engine kW Overload: Enable or Disable, threshold is adjustable from 95 to 140% of Genset kW Rating

in 1% increments.

G

Low Fuel Level: Enable or Disable, threshold is adjustable from 10 to 100% in 1 % increments.

H

High Coolant Temp: Enable or Disable, threshold is adjustable from 100 to 280

F or 38 to 138C in 1

increments. Activation time delay is fixed at 60 s.

I

Low Coolant Temp: Enable or Disable, threshold is adjustable from 35 to 150

F or 2 to 65C in 1

increments.

J

Low Coolant Level: Enable or Disable, threshold is adjustable from 1 to 99% in 1 % increments.

K

Low Oil Pressure: Enable or Disable, threshold is adjustable from 3 to 150 psi or 21 to 1,034 kPa in 7

psi or kPa increments. Activation time delay is fixed at 10 s.

L

ECU Coms Fail: Enable or Disable.

M

Active DTC: Enable or Disable.

N

AVR Bias Output Limit: Enable or Disable, activation delay is adjustable from 1 to 15 seconds in 1

second increments.

O

GOV Bias Output Limit: Enable or Disable, activation delay is adjustable from 1 to 15 seconds in 1

second increments.

P

Intergenset Comm Failure: Enable or Disable.

Q

LSM Comm Failure: Enable or Disable.

R

ID Missing: Enable or Disable.

S

ID Repeat: Enable or Disable.

T

CEM Comm Failure: Enable or Disable.

U

AEM Comm Failure: Enable or Disable.

V

Checksum Failure: Enable or Disable.

Alarms
An alarm is annunciated when a condition programmed to trigger an alarm is detected. When an alarm
condition exists, the front panel Alarm indicator lights, the Horn output (if programmed and enabled)
energizes, and the cause of the alarm is displayed on the front panel LCD. An alarm condition stops the
engine by opening the Fuel output contact. Alarms are reset when the DGC-2020 is set to Off mode.
Each DGC-2020 alarm is described in the following paragraphs. Alarms may be enabled and adjusted in
BESTCOMSPlus or through the front panel HMI.
BESTCOMSPlus alarm settings (DGC-2020, Alarm Configuration, Alarms) are illustrated in Figure 4-39.

High Coolant Temperature
High coolant temperature alarm settings

A

consist of an enable/disable setting and a threshold setting. If

enabled, a high coolant temperature alarm is triggered instantaneously when the engine coolant
temperature exceeds the threshold setting. The arming delay disables the high coolant temperature alarm
function for a user-adjustable time during engine startup.

Low Oil Pressure
Low oil pressure alarm settings

B

include an enable/disable setting, an arming time delay, and a threshold

setting. If enabled, a low oil pressure alarm is triggered instantaneously when the engine oil pressure
decreases below the threshold setting. The arming delay disables the low oil pressure alarm function for a
user-adjustable time during engine startup.

Overspeed
Overspeed alarm settings

C

include an enable/disable setting, an activation delay, and a threshold setting.

If enabled, an overspeed alarm occurs when the engine speed (in rpm) exceeds the threshold setting for
the duration of the activation time delay.

Low Fuel Level
Low fuel level alarm settings

D

consist of an enable/disable setting, an activation delay setting, and a

threshold setting. If enabled, a low fuel level alarm is triggered when the metered fuel level drops below
the threshold setting for the duration of the activation time delay.

Low Coolant Level
Low coolant level alarm settings

E

consist of an enable/disable setting and a threshold setting. If enabled,

a low coolant level alarm is triggered when the metered coolant drops below the threshold setting.