CANbus Interface

These terminals provide communication using the SAE J1939 protocol and provide high-speed
communication between the LSM-2020 and the DGC-2020. Connections between the LSM-2020 and
DGC-2020 should be made with twisted-pair, shielded cable. CANbus interface terminals are listed in
Table 8-4. Refer to Figure 8-4 and Figure 8-5.

Table 8-4. CANbus Interface Terminals

Terminal Description

P2-12 (CAN L)

CAN low connection (green wire)

P2-11 (CAN H)

CAN high connection (yellow wire)

P2-10 (SHIELD)

CAN drain connection

NOTES

1.) If the LSM-2020 is providing one end of the J1939 bus, a 120

 terminating

resistor should be installed across terminals P2-12 (CANL) and P2-11
(CANH).

2.) If the LSM-2020 is not part of the J1939 bus, the stub connecting the LSM-

2020 to the bus should not exceed 914 mm (3 ft) in length.

3.) The maximum bus length, not including stubs, is 40 m (131 ft).

4.) The J1939 drain (shield) should be grounded at one point only. If grounded

elsewhere, do not connect the drain to the LSM-2020.

AEM-2020

(Optional)

LSM-2020

Other

Devices

P0053-58

Engine

120 ohm

Termination

CAN-H

CAN-L

CEM-2020

(Optional)

DGC-2020

120 ohm

Termination

Bus

Stub

Figure 8-4. CANbus Interface with LSM-2020 providing One End of the Bus

9400200990 Rev K