Pulse outputs, Bus condition detection – Winco DGC-2020 User Manual

Page 300

Advertising
background image

B-24 DGC-2020

Modbus

Communication

9400200990 Rev K

Register Description

Type

Units

Scaling

Factor

R/W

Range

42328

kw Integrator Limit Plus

Float

N/A

N/A

RW

0 - 1000

42330

kw Integrator Limit Minus

Float

N/A

N/A

RW

(-1000) - 0

42332

kw Output Upper Limit

Float

N/A

N/A

RW

0 - 1000

42334

kw Output Lower Limit

Float

N/A

N/A

RW

(-1000) - 0

42336 RESERVED

42338

Droop Percent

Float

Percent

N/A

RW

0 - 10

42340

Load Control

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

42342

kw Load Rate

Int32

N/A

Deci

RW

0 - 1000

42344

Breaker Open Setpoint

Int32

N/A

Deci

RW

0 - 1000

42346

AVR Bias Control Output Type

Int32

N/A

N/A

RW

0 = Contact
1 = Analog

42348

Governor Bias Control Output Type

Int32

N/A

N/A

RW

0 = Contact
1 = Analog

42350

Speed Droop Gain

Float

N/A

N/A

RW

0 - 1000

42352

Voltage Droop Gain

Float

N/A

N/A

RW

0 - 1000

42354

Speed Trim Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

42356

Voltage Trim Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

42358

Ramped Watt Demand Per Unit

Float

N/A

N/A

R

0 - 100

42360

Watt Demand Per Unit

Float

N/A

N/A

R

0 - 100

42362

Speed PID Output

Float

N/A

N/A

R

0 - 100

42364

kw PID Output

Float

N/A

N/A

R

0 - 100

42366

Volt PID Output

Float

N/A

N/A

R

0 - 100

42368

Speed Trim Setpoint

Int32

DeciHertz

Deci

RW

470 - 4400

42370-498 FUTURE

USE

Pulse Outputs

Register Description

Type

Units

Scaling

Factor

R/W

Range

42500

AVR Correction Pulse Width

Int32

Decisecond

Deci

RW

0 - 999

42502

AVR Correction Pulse Interval

Int32

Decisecond

Deci

RW

0 - 999

42504

AVR Bias Contact Type

Int32

N/A

N/A

RW

0 = Continuous
1 = Proportional

42506 RESERVED

42508

Governor Correction Pulse Width

Int32

Decisecond

Deci

RW

0 - 999

42510

Governor Correction Pulse Interval

Int32

Decisecond

Deci

RW

0 - 999

42512

Governor Bias Contact Type

Int32

Decisecond

Deci

RW

0 = Continuous
1 = Proportional

42514 RESERVED

42516-748 FUTURE

USE

Bus Condition Detection

Register Description

Type

Units

Scaling

Factor

R/W

Range

42750

Gen Sensing Dead Bus Pickup

Int32

Volt

N/A

RW

0 - 4800

42752

Gen Sensing Dead Bus Time Delay

Int32

Decisecond

Deci

RW

1 - 6000

42754 RESERVED

42756

Gen Sensing Stable Undervoltage Pickup

Int32

Volt

N/A

RW

10 - 99999

42758

Gen Sensing Stable Undervoltage Dropout

Int32

Volt

N/A

RW

10 - 99999

42760

Gen Sensing Stable Overvoltage

Int32

Volt

N/A

RW

10 - 99999

42762

Gen Sensing Stable Overvoltage Dropout

Int32

Volt

N/A

RW

10 - 99999

42764

Gen Sensing Stable Underfrequency Pickup

Int32

CentiHertz

Centi

RW

4600 - 6400

42766

Gen Sensing Stable Underfrequency Dropout

Int32

CentiHertz

Centi

RW

4600 - 6400