APPENDIX A

TIME OVERCURRENT

CHARACTERISTIC CURVES

INTRODUCTION

The inverse time overcurrent characteristic curves provided by the DGC-2020 (style xxxxxxExx only)
closely emulate most of the common electromechanical, induction-disk, overcurrent relays sold in North
America. To further improve proper relay coordination, selection of integrated reset or instantaneous
reset characteristics is also provided.

CURVE SPECIFICATIONS

Timing Accuracy:

Within ±500 milliseconds of indicated operating
point.


Sixteen inverse time functions and one fixed time
function can be selected. Characteristic curves for
the inverse and definite time functions are defined
by the following equation:

K

BD

C

M

AD

T

N

T

Equation A-1

1

M

RD

T

2

R

Equation A-2


T

T

= Time to trip when M

 1

T

R

= Time to reset if relay is set for integrating

reset when M

 1. Otherwise, reset is 50

milliseconds or less

D

= TIME DIAL setting (0.0 to 9.9)

M

= Multiple of PICKUP setting (0 to 40)

A, B, C, N, K

= Constants for the particular curve

R

= Constant defining the reset time

This

equation

complies

with

IEEE

Standard

C37.112-1996.

 Timing range is 0.0 to 7,200 seconds when the
F (fixed) curve is selected.


Table

A-1

lists

time

characteristic

curve

constants. See Figures A-1 through A-16 for
graphs of the characteristics.

9400200990 Rev K

DGC-2020 Time Overcurrent Characteristic Curves