Overvoltage (59-1, 59-2), Figure 4-41. undervoltage protection settings -45 – Winco DGC-2020 User Manual

Page 115

Advertising
background image

The hysteresis setting

D

functions as an undervoltage dropout by preventing rapid switching of the pickup

output.
A frequency-based inhibit setting

E

prevents a 27 trip from occurring during an undervoltage condition

associated with system startup.
A low-line scale factor setting

F

is used to automatically adjust the undervoltage pickup settings in

applications that may utilize more than one type of genset connections. The scale factor setting is
implemented when the DGC-2020 senses a contact closure at a contact input programmed to activate
scaling of the protection settings. The value of the scale factor setting serves as a multiplier for the pickup
settings. For example, if a scale factor contact input is received by the DGC-2020 and the scale factor
setting is 2.000, the pickup setting will be doubled (2.000

 PU).

The element is disabled when Alarm Configuration is set to “None”. Element status is available in
BESTlogic+ Programmable Logic when “Status Only” is selected.
BESTCOMSPlus voltage protection settings (DGC-2020, Generator Protection, Voltage, Undervoltage)
are illustrated in Figure 4-41. The 27-1 element is shown.

Figure 4-41. Undervoltage Protection Settings

A

Pickup: Adjustable from 70 to 576 Vac in 1 Vac increments.

B

Activation Delay:

Adjustable from 0 to 30 s in 0.1 s increments.

C

Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only.

D

Hysteresis: Adjustable from 1 to 60 Vac in 1 Vac increments.

E

Inhibit Frequency: Adjustable from 20 to 400 Hz in 1 Hz increments.

F

Low Line Scale Factor: Adjustable from 0 to 3.000 in increments of 0.001.

Overvoltage (59-1, 59-2)
Two sets of overvoltage settings are provided for each element: one for three-phase generator
connections and one for single-phase generator connections. The pickup setting entered is based on the
VT secondary side (DGC-2020). When a single-phase override contact input is received, the DGC-2020
automatically switches from the three-phase overvoltage settings to the single-phase overvoltage
settings.
An overvoltage condition is annunciated when the average of the three-phase (three-phase mode) or the
line-to-line voltage (single-phase mode) increases above the corresponding 59 pickup setting

A

for the

duration of the corresponding 59 activation delay

B

. An overvoltage annunciation can be user-selected to

trigger a pre-alarm

C

(warning) or alarm

C

(shutdown). An overvoltage annunciation can also be user-

configured to close a programmable output.
The hysteresis setting

D

functions as an undervoltage dropout by preventing rapid switching of the pickup

output.
A low-line scale factor setting

E

is used to automatically adjust the overvoltage pickup settings in

applications that may utilize more than one type of genset connections. The scale factor setting is
implemented when the DGC-2020 senses a contact closure at a contact input programmed to activate
scaling of the protection settings. The value of the scale factor setting serves as a multiplier for the pickup

9400200990 Rev K