Operating power, Aem-2020 inputs and outputs, Operating power -5 – Winco DGC-2020 User Manual

Page 249: Aem-2020 inputs and outputs -5, Figure 10-2. input and output terminals -5, Table 10-1. operating power terminals -5

Advertising
background image

is mounted permanently to the board. Connector screw terminals accept a maximum wire size of 12
AWG. Thermocouple connectors accept a maximum thermocouple wire diameter of 0.177 inches (4.5
mm). Maximum screw torque is 5 inch-pounds (0.56 N

m).

Operating Power

The Analog Expansion Module operating power input accepts either 12 Vdc or 24 Vdc and tolerates
voltage over the range of 6 to 32 Vdc. Operating power must be of the correct polarity. Although reverse
polarity will not cause damage, the AEM-2020 will not operate. Operating power terminals are listed in
Table 10-1.

It is recommended that a fuse be added for additional protection for the wiring to the battery input of the
Analog Expansion Module. A Bussmann ABC-7 fuse or equivalent is recommended.

Table 10-1. Operating Power Terminals

Terminal Description

P1-

(SHIELD)

Chassis ground connection

P1- – (BATT–)

Negative side of operating power input

P1- + (BATT+)

Positive side of operating power input

AEM-2020 Inputs and Outputs

Input and output terminals are shown in Figure 10-2 and listed in Table 10-2.

.

Figure 10-2. Input and Output Terminals

9400200990 Rev K

DGC-2020 AEM-2020 (Analog Expansion Module)

10-5

Advertising