A-2

DGC-2020 Time Overcurrent Characteristic Curves

9400200990 Rev K

Table A-1. 51 Time Characteristic Curve Constants

Trip Characteristic Constants

Reset

Curve

Selection

Curve Name

A B C N K R

S1

S, S1, Short Inverse

0.2663

0.03393

1.0000

1.2969

0.0280

0.5000

S2

S2, Short Inverse

0.0286

0.02080

1.0000

0.9844

0.0280

0.0940

L1

L, L1, Long Inverse

5.6143

2.18592 1.0000 1.0000 0.0280 15.750

L2

L2, Long Inverse

2.3955

0.00000

1.0000

0.3125

0.0280

7.8001

D

D, Definite Time

0.4797

0.21359

1.0000

1.5625

0.0280

0.8750

M

M, Moderately Inverse

0.3022 0.12840 1.0000 0.5000 0.0280 1.7500

I1

I, I1, Inverse Time

8.9341

0.17966

1.0000

2.0938

0.0280

9.0000

I2

I2, Inverse Time

0.2747

0.10426

1.0000

0.4375

0.0280

0.8868

V1

V, V1, Very Inverse

5.4678

0.10814

1.0000

2.0469

0.0280

5.5000

V2

V2, Very Inverse

4.4309

0.09910

1.0000

1.9531

0.0280

5.8231

E1

E, E1Extremely Inverse

7.7624 0.02758 1.0000 2.0938 0.0280 7.7500

E2

E2, Extremely Inverse

4.9883

0.01290

1.0000

2.0469

0.0280

4.7742

A

A, Standard Inverse

0.01414

0.00000 1.0000 0.0200 0.0280 2.0000

B

B, Very Inverse (I

2

t)

1.4636 0.00000 1.0000 1.0469 0.0280 3.2500

C

C, Extremely Inverse (I

2

t)

8.2506 0.00000 1.0000 2.0469 0.0280 8.0000

G

G, Long Time Inverse (I

2

t)

12.1212

0.00000 1.0000 1.0000 0.0280 29.0000

F

Fixed Time

0.0000 1.00000 0.0000 0.0000 0.0280 1.0000

 Curve F has a fixed delay of one second times the Time Dial setting.

TIME OVERCURRENT CHARACTERISTIC CURVE GRAPHS

Figures A-1 through A-16 illustrate the characteristic curves of the DGC-2020. Table A-2 cross-
references each curve to existing electromechanical relay characteristics. Equivalent time dial settings
were calculated at a value of five times pickup.