Remote outputs status bits, Cem alarm bits, Remote configurable inputs pre-alarm bits – Winco DGC-2020 User Manual

Page 317: Remote configurable inputs alarm bits, Aem alarm bits, Reserved, Generator frequency, Bus frequency, Power factor, Ecu lamp status

Advertising
background image

9400200990 Rev K

DGC-2020 Modbus

Communication

B-41

Register Description Type

Units

Scaling

Factor

R/W Range

44966

Remote Outputs Status
Bits

Int32

N/A

N/A

R

Bit 0 = Remote Output 13
Bit 1 = Remote Output 14
Bit 2 = Remote Output 15
Bit 3 = Remote Output 16
Bit 4 = Remote Output 17
Bit 5 = Remote Output 18
Bit 6 = Remote Output 19
Bit 7 = Remote Output 20
Bit 8 = Remote Output 21
Bit 9 = Remote Output 22
Bit 10 = Remote Output 23
Bit 11 = Remote Output 24
Bit 12 = Remote Output 25
Bit 13 = Remote Output 26
Bit 14 = Remote Output 27
Bit 15 = Remote Output 28
Bit 16 = Remote Output 29
Bit 17 = Remote Output 30
Bit 18 = Remote Output 31
Bit 19 = Remote Output 32
Bit 20 = Remote Output 33
Bit 21 = Remote Output 34
Bit 22 = Remote Output 35
Bit 23 = Remote Output 36

44968

CEM Alarm Bits

Uint32 N/A

N/A

R

Bit 0 = CEM Comm Fail
Bit 1 = Duplicate CEM
Bit 2 = CEM Hardware Mismatch

44970

Remote Configurable
Inputs Pre-Alarm Bits

Uint32 N/A

N/A

R

Bit 0 = Remote Input 17
Bit 1 = Remote Input 18
Bit 2 = Remote Input 19
Bit 3 = Remote Input 20
Bit 4 = Remote Input 21
Bit 5 = Remote Input 22
Bit 6 = Remote Input 23
Bit 7 = Remote Input 24
Bit 8 = Remote Input 25
Bit 9 = Remote Input 26

44972

Remote Configurable
Inputs Alarm Bits

Uint32 N/A

N/A

R

Bit 0 = Remote Input 17
Bit 1 = Remote Input 18
Bit 2 = Remote Input 19
Bit 3 = Remote Input 20
Bit 4 = Remote Input 21
Bit 5 = Remote Input 22
Bit 6 = Remote Input 23
Bit 7 = Remote Input 24
Bit 8 = Remote Input 25
Bit 9 = Remote Input 26

44974

AEM Alarm Bits

Uint32 N/A

N/A

R

Bit 0 = AEM Comm Fail
Bit 1 = Duplicate AEM

44976-84

RESERVED

44986

Generator Frequency

Int32

N/A

Deci

R

0 - 4400

44988

Bus Frequency

Int32

N/A

Deci

R

0 - 440

44990

Power Factor

Int32

N/A

Centi

R

(-100) - 100

44992-99

RESERVED

45000

ECU Lamp Status

Int32

N/A

N/A

R

Bit 24 = Malfunction
Bit 27 = Stop
Bit 28 = Warning
Bit 31 = Protect

45002

Number of DTC’s

Int32

N/A

N/A

R

(-32768) - 32767

45004-490

RESERVED

45500

Analog Input 1 Metering
Value

Int32 DeciUnit

Deci R (-99990)

-

99990

45502

Analog Input 2 Metering
Value

Int32 DeciUnit

Deci R (-99990)

-

99990