Multigen management, Avr output, Governor output – Winco DGC-2020 User Manual

Page 130: Multigen management -60, Avr output -60, Governor output -60, Figure 4-54. avr output settings -60

Advertising
background image

P

Derivative Filter Constant (Td): Adjustable from 0 to 1 in increments of 0.001.

Q

Loop Gain (Kg): Adjustable from 1 to 1,000 in increments of 0.001.

R

Droop Percentage: Adjustable from 0 to 10 percent in 0.001 % increments.

S

Speed Droop Gain: Adjustable from 0 to 1,000 in increments of 0.001.

T

Ramp Rate: Adjustable from 0 to 100 percent/second in 0.1 %/s increments.

U

Base Load Level Source: User Setting, LSM Analog Input 1, or Analog Inputs 1-8.

V

Base Load Level: Adjustable from 0 to 100 percent in 1 % increments.

W

Baseload Analog Max: Adjustable from 0 to 100 percent in 0.1 % increments.

X

Baseload Analog Min: Adjustable from 0 to 100 percent in 0.1% increments.

Y

Breaker Open Setpoint: Adjustable from 0 to 1,000 in increments of 1.

MULTIGEN MANAGEMENT

This group of settings is used when an optional LSM-2020 (Load Share Module) is connected to the
DGC-2020. Multigen management settings consist of settings for AVR output, governor output, load
share output, demand start/stop, generator sequencing, and network configuration.

AVR Output
The AVR output

A

of the LSM-2020 is used to change the voltage setpoint of the generator. If the

response

B

is set for increasing, an increased bias will cause higher voltage. If the response

B

is set for

decreasing, an increased bias will cause lower voltage. Settings are provided for minimum output
current

C

, maximum output current

D

, minimum output voltage

E

, and maximum output voltage

F

.

BESTCOMSPlus AVR output settings (DGC-2020, Multigen Management, AVR Output) are illustrated in
Figure 4-54.

Figure 4-54. AVR Output Settings

A

Output Type: Voltage or Current.

B

Response: Increasing or Decreasing.

C

Min Output Current: Adjustable from 4 to 20 mA in 0.1 mA increments.

D

Max Output Current: Adjustable from 4 to 20 mA in 0.1 mA increments.

E

Min Output Voltage: Adjustable from –10 to +10 V in 0.1 V increments.

F

Max Output Voltage: Adjustable from –10 to +10 V in 0.1 V increments.

Governor Output
The governor output

A

of the LSM-2020 is used to change the speed setpoint of the generator. If the

response

B

is set for increasing, an increased bias will cause faster speed. If the response

B

is set for

decreasing, an increased bias will cause slower speed. Settings are provided for minimum output
current

C

, maximum output current

D

, minimum output voltage

E

, and maximum output voltage

F

.

BESTCOMSPlus governor output settings (DGC-2020, Multigen Management, Governor Output) are
illustrated in Figure 4-55.

4-60