 Overspeed

Alarm

 Scheduled Maintenance Pre-Alarm

 Switch Not in Auto

 Transfer Fail Alarm

 Virtual Output X Status (X = 1 to 8)

 Weak Battery Voltage Pre-Alarm

Dial-Out
The DGC-2020 uses telelocator alphanumeric protocol (TAP) version 1.7 when communicating with
paging companies. This data format

D

specifies seven data bits with even parity. If required, eight data bits

with no parity may be specified.
The message string sent by the DGC-2020 can be limited to a length supported by the receiving pagers

E

.

If a message to be transmitted by the DGC-2020 exceeds the pager message limit, the DGC-2020 will
make multiple calls to transmit the complete message.
Dial-out messages are sent by the DGC-2020 at a user-defined interval

F

. This interval gives an operator

the opportunity to dial into the DGC-2020. A second user-defined interval

G

determines how frequently

dial-out attempts are made following a dial-out failure.

Dial-In
When the DGC-2020 modem shares a line used for voice communication, the number of rings

H

required

for the modem to answer can be increased to allow time for an operator to answer an incoming telephone
call.

Figure 4-18. Modem Setup

A

Dial Out Number: Accepts a telephone number of up to 16 characters.

B

Pager ID: Accepts a pager identification number of up to 16 characters.

C

Modem Dialout Conditions: Check boxes to select conditions that will initiate a dial-out message.

D

Pager Coms Data Format: 7 bit – Even Parity or 8 bit – No Parity.

E

Pager Buffer Limit: Adjustable from 80 to 200 characters in increments of 40.

F

Modem Offline Delay: Adjustable from 1 to 240 min in 1 min increments.

G

Inter Dialout Activation Delay: A delay of 15, 30, 60, or 120 s may be selected.

H

Rings for Modem Answer: Adjustable from 1 to 9 in increments of 1.

RS-485 Setup (Optional)
DGC-2020 controllers with the optional RS-485 communication port (style number xxxRxxxxx) can be
monitored and controlled via a polled network using the Modbus protocol. Adjustable RS-485 port settings
include the baud rate

A

, parity

B

, and port address

C

. Fixed RS-485 port settings include the number of data

bits (8) and stop bits (1).
Modbus register values for the DGC-2020 are listed and defined in Appendix B, Modbus Communication.
BESTCOMSPlus RS-485 port settings are illustrated in Figure 4-19.

4-20

DGC-2020 BESTCOMSPlus Software

9400200990 Rev K