Establishing communication, Establishing communication -7 – Winco DGC-2020 User Manual

Page 77

Advertising
background image

10.0.0.0

-

10.255.255.255

172.16.0.0

-

172.31.255.255

192.168.0.0

-

192.168.255.255

If the LSM-2020 is operating on an isolated network, the Subnet Mask may be left at 0.0.0.0 and the
Default Gateway

can be chosen as any valid IP address from the same range as the LSM-2020 IP

address.

3. Click

the

Send to Device

button located on the Configure Ethernet Port screen. A confirmation popup

will be displayed notifying the user that the LSM-2020 will reboot after settings are sent. Click the Yes
button to allow settings to be sent. After the unit has rebooted and the power-up sequence is
complete, the LSM-2020 is ready to be used on a network.

4. If desired, LSM-2020 settings can be verified by selecting Download Settings and Logic from the

Communication

pull-down menu. Active settings will be downloaded from the LSM-2020 and DGC-

2020. Verify that the downloaded settings match the previously sent settings.

5. Connection to the DGC-2020 can be made through Ethernet via an LSM-2020 with properly

configured network settings. When making a new connection to the DGC-2020, the Ethernet
Connection

option shown in Figure 4-7 will allow the user to enter the IP address of the LSM-2020

with which to connect. The Ethernet button under Device Discovery, Scan for Connected Devices,
allows automatic detection of any LSM-2020 devices connected to the local network.

NOTE

The PC running BESTCOMSPlus software must be correctly configured to
communicate with the LSM-2020. The PC must have an IP address in the same
subnet range as the LSM-2020 if the LSM-2020 is operating on a private local
network. Otherwise, the PC must have a valid IP address with access to the
internet and the LSM-2020 must be connected to a properly configured router.
The network settings of the PC depend on the operating system installed. Refer
to the operating system manual for instructions. On most Microsoft

Windows

based PCs, the network settings can be accessed through the Network
Connections

icon located inside the Control Panel.

NOTE

Microsoft Windows 2000 and XP SP1 contain a potential bug that may prevent
device discovery from functioning properly. This issue may present itself if the PC
running BESTCOMSPlus has more than one network interface card. See
Microsoft

KB article 827536 for more information.

NOTE

Firmware updates to the LSM-2020 are made through the Ethernet port.
Firmware updates to the DGC-2020 are only available through the USB port of
the DGC-2020.

Establishing Communication
Communication between BESTCOMSPlus and the DGC-2020 is established by clicking on the Connect
button on the DGC-2020 Connection screen (see Figure 4-7) or by clicking on the Connect button on the
lower menu bar of the main BESTCOMSPlus screen (Figure 4-1). If you receive an “Unable to Connect to
Device” error message, verify that communications are configured properly. If communication is
established, BESTCOMSPlus will automatically read all settings and logic from the DGC-2020 and load
them into BESTCOMSPlus memory. See Figure 4-10.

9400200990 Rev K

DGC-2020 BESTCOMSPlus Software

4-7