Overcurrent protection (51-1, 51-2, 51-3), Overcurrent protection (51-1, 51-2, 51-3) -50 – Winco DGC-2020 User Manual

Page 120

Advertising
background image

4-50

DGC-2020 BESTCOMSPlus Software

9400200990 Rev K

Overcurrent Protection (51-1, 51-2, 51-3)
Two sets of overcurrent settings are provided for each element: one for three-phase generator
connections and one for single-phase generator connections. The pickup setting entered is based on the
CT secondary side (DGC-2020). When a single-phase override contact input is received by the DGC-
2020, the overcurrent protection settings automatically switch from the three-phase settings to the single-
phase overcurrent protection settings.
When any of the phase currents increase above the pickup setting

A

for the duration of the overcurrent

time delay, an overcurrent condition is annunciated. An overcurrent annunciation can be user-selected to
trigger a pre-alarm

B

(warning) or alarm

B

(shutdown). An overcurrent annunciation can also be user-

configured to close a programmable output.
The overcurrent time delay is controlled by a time dial setting

C

and a curve setting

D

. The curve setting can

be set at F (fixed) or one of 16 inverse time characteristic curves can be selected. When the fixed curve
setting is selected, the time dial setting determines the overcurrent time delay with no regard to the
generator current level. When one of the inverse time characteristic curves is selected, the time dial
setting, along with the level of measured generator current, determines the overcurrent time delay. As
overcurrent protection settings are entered in BESTCOMSPlus, a plot

E

of the settings is automatically

created to illustrate the overcurrent pickup curve. The available time characteristic curves are listed below
and illustrated in Appendix A, Time Overcurrent Characteristic Curves.
 A, standard inverse

 I2,

inverse

 A, standard inverse

 I2,

inverse

 B, very inverse

 L1, long inverse

 C, extremely inverse

 L2, long inverse

 D,

definite

 M, moderately inverse

 E1, extremely inverse

 S1, short inverse

 E2, extremely inverse

 S2, short inverse

 G, long inverse

 V1, very inverse

 I1,

inverse

 V2, very inverse

A low-line scale factor setting

F

is used for automatic adjustment of the overcurrent pickup settings in

applications that may utilize more than one type of genset connections. The scale factor setting is
implemented when the DGC-2020 senses a contact closure at a contact input programmed to activate
scaling of the protection settings. The value of the scale factor setting serves as a multiplier for the pickup
settings. For example, if a scale factor contact input is received by the DGC-2020 and the scale factor
setting is 2.000, the pickup setting will be doubled (2.000

 PU).

The graph can be set

G

to display the 1 Phase or 3 Phase curve as determined by the settings on the left

side of the chart.
Selection of integrated reset or instantaneous reset characteristics

H

is also provided. Refer to Appendix A,

Time Overcurrent Characteristic Curves,

when calculating time to reset.

The element is disabled when Alarm Configuration is set to “None”. Element status is available in
BESTlogic+ Programmable Logic when “Status Only” is selected.
BESTCOMSPlus overcurrent protection settings (DGC-2020, Generator Protection, Overcurrent) are
illustrated in Figure 4-48. The 51-1 element is shown.