Cumulative number of engine starts, Session start date month, Session start date day – Winco DGC-2020 User Manual

Page 315: Session start date year, Generator status, 8 = connecting state, Future use, Reserved, Global alarm, Global pre-alarm

Advertising
background image

9400200990 Rev K

DGC-2020 Modbus

Communication

B-39

Register Description Type

Units

Scaling

Factor

R/W Range

44858

Session Total Engine Run
Hrs.

Int32

Hour

N/A

R

0 - 99999

44860

Session Total Engine Run
Min.

Int32

N/A

N/A

R

0 - 59

44862

Session Loaded Engine
Run Hrs.

Int32

Hour

N/A

R

0 - 99999

44864

Session Loaded Engine
Run Min.

Int32

N/A

N/A

R

0 - 59

44866

Session Unloaded Engine
Run Hrs.

Int32

Hour

N/A

R

0 - 99999

44868

Session Unloaded Engine
Run Min.

Int32

N/A

N/A

R

0 - 59

44870

Session kW-Hrs

Int32

KiloWattHour

N/A

R

0 - 999999999

44872

Cumulative Number of
Engine Starts

Uint32 N/A

N/A

RW

0 - 65535

44874

Session Start Date Month

Uint32 N/A

N/A

RW

1 - 12

44876

Session Start Date Day

Uint32 N/A

N/A

RW

1 - 31

44878

Session Start Date Year

Uint32 N/A

N/A

RW

0 - 99

44880

Generator Status

Uint32 N/A

N/A

R

0 = RESET State
1 = READY State
2 = CRANKING State
3 = RESTING State
4 = RUNNING State
5 = ALARM State
6 = PRESTART State
7 = COOLING State
8 = CONNECTING State
9 = DISCONNECT State
10 = PULSING State
11 = UNLOADING State

44882-918

FUTURE USE

44920-48

RESERVED

44950

Global Alarm

Uint32 N/A

N/A

R

0 = No system alarms in effect
1 = System alarm(s) in effect

44952

Global Pre-Alarm

Uint32 N/A

N/A

R

0 = No system pre-alarms in effect
1 = System pre-alarm(s) in effect

44954

Local Configurable Inputs
Pre-Alarm Bits

Int32

N/A

N/A

R

Bit 0 = Input 1
Bit 1 = Input 2
Bit 2 = Input 3
Bit 3 = Input 4
Bit 4 = Input 5
Bit 5 = Input 6
Bit 6 = Input 7
Bit 7 = Input 8
Bit 8 = Input 9
Bit 9 = Input 10
Bit 10 = Input 11
Bit 11 = Input 12
Bit 12 = Input 13
Bit 13 = Input 14
Bit 14 = Input 15
Bit 15 = Input 16

Advertising