Installation, Product registration, Mounting – Winco DGC-2020 User Manual

Page 226: Installation -6, Product registration -6, Mounting -6, Figure 8-2. device security setup screen -6

Advertising
background image

Figure 8-2. Device Security Setup Screen

A

Access Level/Password: Read-only value obtained when BESTCOMSPlus is communicating with the

Load Share Module.

B

Password: Accepts an alphanumeric character string of up to 16 characters.

C

Save Password: Clicking this button will save the password changes in BESTCOMSPlus memory.

INSTALLATION

LSM-2020’s are delivered in sturdy cartons to prevent shipping damage. Upon receipt of a module, check
the part number against the requisition and packing list for agreement. Inspect for damage, and if there is
evidence of such, immediately file a claim with the carrier and notify the Basler Electric regional sales
office, your sales representative, or a sales representative at Basler Electric, Highland, Illinois USA.

If the device is not installed immediately, store it in the original shipping package in a moisture- and dust-
free environment.

Product Registration

Registering with Basler Electric enables you to receive important information updates on your product
plus new product announcements. Register your product by directing your web browser to

www.basler.com

.

Mounting

LSM-2020’s are contained in an encapsulated plastic case and may be mounted in any convenient
position. The construction of a LSM-2020 is durable enough to mount directly on a genset using UNF ¼-
20 or equivalent hardware. Hardware selection should be based on any expected shipping/transportation
and operating conditions. The torque applied to the mounting hardware should not exceed 65 in-lb (7.34
N•m).

See Figure 8-3 for LSM-2020 overall dimensions. All dimensions are shown in inches with millimeters in
parenthesis.

8-6

DGC-2020 LSM-2020 (Load Share Module)