Pre-start contact config, System units, Battery volts – Winco DGC-2020 User Manual

Page 302: Off mode status, Run mode status, Auto mode status, Virtual input 1 status, Virtual input 2 status, Virtual input 3 status, Virtual input 4 status

Advertising
background image

B-26 DGC-2020

Modbus

Communication

9400200990 Rev K

Register Description Type

Units

Scaling

Factor

R/W Range

43502

Pre-Start Contact Config

Int32

N/A

N/A

RW

0 = Open After Disconnect
1 = Closed While Running

43504

System Units

Int32

N/A

N/A

RW

0 = English
1 = Metric

43506

Battery Volts

Int32

N/A

N/A

RW

0 = 12V
1 = 24V

43508

Off Mode Status

Int32

N/A

N/A

R

0 = Disable
1 = Enable

43510

Run Mode Status

Int32

N/A

N/A

R

0 = Disable
1 = Enable

43512

Auto Mode Status

Int32

N/A

N/A

R

0 = Disable
1 = Enable

43514

Virtual Input 1 Status

Int32

N/A

N/A

R

0 = Disable
1 = Enable

43516

Virtual Input 2 Status

Int32

N/A

N/A

R

0 = Disable
1 = Enable

43518

Virtual Input 3 Status

Int32

N/A

N/A

R

0 = Disable
1 = Enable

43520

Virtual Input 4 Status

Int32

N/A

N/A

R

0 = Disable
1 = Enable

43522

RTC Clock Hour

Int32

Hour

N/A

RW

0 - 23

43524

RTC Minute

Int32

Minute

N/A

RW

0 - 59

43526

RTC Second

Int32

Second

N/A

RW

0 - 59

43528

RTC Month

Int32

N/A

N/A

RW

1 - 12

43530

RTC Day

Int32

N/A

N/A

RW

1 - 31

43532

RTC Year

Int32

N/A

N/A

RW

0 - 99

43534

RTC DST Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

43536

Gen PT Primary

Int32

Volt

N/A

RW

1 - 99999

43538

Gen PT Secondary

Int32

Volt

N/A

RW

1 - 480

43540

Gen CT Primary

Int32

Amp

N/A

RW

1 - 9999

43542

Bus PT Primary

Int32

Volt

N/A

RW

1 - 99999

43544

Bus PT Secondary

Int32

Volt

N/A

RW

1 - 480

43546

Cranking Style

Uint32

N/A

N/A

RW

0 = Continuous
1 = Cycle

43548

Number of Crank Cycles

Uint32

N/A

N/A

RW

1 - 7

43550

Cycle Crank Time

Unit32

Second

N/A

RW

5 - 15

43552

Continuous Crank Time

Unit32

Second

N/A

RW

5 - 60

43554

Crank Disconnect Limit

Uint32

Percent

N/A

RW

10 - 100

43556

Pre Crank Delay

Uint32

Second

N/A

RW

0 - 30

43558

Configured Gen Connection

Uint32

N/A

N/A

RW

0 = Delta
1 = Wye
2 = 1-phase AB
3 = 1-phase AC
4 = Grounded Delta

43560

Gen Rated Frequency

Int32

Hertz

N/A

RW

0 = 50 Hz
1 = 60 Hz

43562

Rated Kw

Uint32

KiloWatt

N/A

RW

5 - 9999

43564

Rated Engine RPM

Uint32

RPM

N/A

RW

750 - 3600

43566

No Load Cool Down Time

Uint32

Minute

N/A

RW

0 - 60

43568

EPS Current Threshold

Int32

PercentCTPri N/A

RW

3 - 10

43570

Fuel Level Function

Uint32

N/A

N/A

RW

0 = Disable
1 = Fuel Lvl
2 = Natural Gas
3 = Propane

43572

Number Flywheel Teeth

Uint32

N/A

N/A

RW

50 - 500

Advertising